Pad-mount distribution transformers serve underground and pad-mounted laterals, often at utilities, campuses, and data-center sites. They are medium-voltage equipment on the primary. Units are sourced to kVA, high- and low-side voltage, loop or radial configuration, and efficiency requirements in the specification. Three-phase compartmental units are typically specified to IEEE C57.12.34; single-phase pad-mounted units to IEEE C57.12.38.

>1 kV to <100 kV

Category details

Typical ratings and voltage range
Typical ratings from tens of kVA to several thousand kVA, as specified. Primary is in the medium-voltage distribution range (IEEE C57.12.34 covers three-phase units through 10 MVA with primary ≤34.5 kV and secondary ≤15 kV; IEEE C57.12.38 covers single-phase units through 250 kVA with primary 34 500GrdY/19 920 V and below and secondary 480/240 V and below). The secondary is typically ≤600 V, and may be specified up to 15 kV on some three-phase units. Applicable voltage classes: Medium voltage (greater than 1 kV and less than 100 kV).
Standards buyers commonly specify
  • IEEE C57.12.34 (three-phase pad-mounted distribution transformers)
  • IEEE C57.12.38 (single-phase pad-mounted distribution transformers)
  • IEEE C57.12.28
  • DOE 10 CFR 431 Subpart K, where the unit meets the definition in 10 CFR 431.192 (typically primary ≤34.5 kV, secondary ≤600 V, 60 Hz, liquid-immersed 10–5,000 kVA or dry-type 15–5,000 kVA; autotransformers, sealed units, rectifier transformers, and certain other types are excluded and must be checked unit by unit)

These are standards buyers often name in a specification. KVAScout is not a certification body and does not issue listings.

What we review with the supplier
  • Phase (single or three), kVA, and primary/secondary voltage
  • Loop or radial configuration
  • Impedance and enclosure integrity
  • Whether DOE 10 CFR 431 Subpart K applies
  • Nameplate and test records

Values come from the specification or from supplier documents. They are not catalog ratings, stock figures, or prices.

Used in
Renewable generation, Distribution grid, Commercial & industrial, Data centers, Real estate & buildings, Energy storage projects
Supplier listings
No supplier listings are published for this category yet. When listings are added, they will be reviewed against the standards and scope noted on this page, and they will appear here with origin, rating, and documented availability. We do not invent stock, prices, certifications, lead times, or partner names.

How we source

Equipment is sourced from qualified supply chains in the United States, Europe, Japan, Korea, Mexico, and other markets, according to each buyer's origin, funding, and compliance requirements. Whether a given origin is eligible for a project is reviewed with the buyer before a firm quotation. Buyers are primarily in the United States; we also serve qualified buyers in other countries. We do not publish inventory or prices on this site, and we do not list suppliers as partners.